PEARL THERMOSTAT PROGRAMMING

PEARL THERMOSTAT PROGRAMMING

Before you enter programming mode to program the thermostat, the device needs to be in an “off” state. To turn the thermostat off, press the “Mode” button until “Off” appears on the screen.

To enter programming mode: PRESS BETWEEN the hold button and the fan button. Continue to hold and swipe down on the right slider – “01” will display.  When the “01” is displayed, it indicates yo are in “programming mode.”  Use the + and – buttons to advance through the menu options listed below in the “Menu Options” list.

Note, utilizing the MODE button will exit you from the menu.  Utilizing the HOLD button will select the option you desire.

When finished programming, tap the MODE button until the thermostat to EXIT the menu and return to normal operation.

Programming Options

Display Celsius and Fahrenheit……………………….. 1

0- Celsius

1- Fahrenheit (Default)

Heat type (Heat pump / Non Heat pump)…………………. 2

0- Non Heat pump(Default)

1- Heat pump

Heat source (Gas / Electric)…………………………. 3

0- Electric(Default)

1- Gas

Temperature Calibration……………………………… 4

-2.5 – +2.5 Celsius

-4.5 – +4.5 Fahrenheit

(Default) – 0

Set Minimum Heatpoint……………………………….. 5

(Default) – 44 Fahrenheit, 7 Celsius

Set Maximum Heatpoint……………………………….. 6

(Default) – 86 Fahrenheit, 30 Celsius

Set Minimum Coolpoint……………………………….. 7

(Default) – 44 Fahrenheit, 7 Celsius

Set Maximum Coolpoint……………………………….. 8

(Default) – 86 Fahrenheit, 30 Celsius

Set Minimum Deadband………………………………… 9

(Default) – 1.8 Fahrenheit, 1.0 Celsius

Sequence of Operation……………………………….. 10

0- Cool Only

1- Cool with reheat

2- Heat Only

3- Heat with reheat

4- Full Auto

5- Full Auto with reheat

6- Manual (Default)

7- Auto Only

EZ Mode……………………………………………. 11

0- No

1- Yes

Join Network……………………………………….. 12

0- No

1- Yes

Leave Network………………………………………. 13

11- Yes

All others – No

Rejoin Network……………………………………… 14

0- No

1- Yes

Redetect System Type………………………………… 15

0- No

1- Yes

Types Detected

04 – HP TWO COOL TWO HEAT

05 – TWO COOL TWO HEAT

FF – INVALID RELAY CONFIGURATION

Reset……………………………………………… 16

0- No

1- Yes

Factory Reset All…………………………………… 17

11- Yes

All others – No

Display Configuration and Network Settings…………….. 18

Order of Display:

1- PSOC Version Number

2- Ember Version Number

3- Heat Type

4- Heat Source

5- Temperature Calibration

6- Relays Detected

7- Network State

8- Network Channel

9-10- PanID

Reset Counter………………………………………. 19

0-

1- Reset to 0